Abstract: According to the principle, characteristics and installation mode of the open-type Hall current sensor, the application of the open-type Hall current sensor in the transformation and distribution system of the factory is analyzed, so as to provide a solution for users to realize the intelligent distribution of DC system quickly.

 

Key words: open type Hall current sensor  DC distribution system  working principle  application

 

0 Overview
  DC distribution system is usually composed of high frequency switching power supply and battery, which is used to provide reliable DC power supply for control, signal, relay protection and automatic devices, accident lighting and so on in DC system. It has high requirements for the reliability, stability and quality of power supply. Therefore, in the Russian DC system, we matched the DC Hall distribution meter used. During the transformation of DC system, there is no power outage, and the engineering transformation is difficult, and the traditional closed Hall current sensor or shunt can not solve the problem. Therefore, the open Hall current sensor can be used to solve the DC current measurement problem in the transformation project, so as to ensure the safe operation of the transformation process without power outage.

 

1 Product Design   
1.1Structural features     

  Open-mouth Hall current sensor is developed on the basis of traditional closed-mouth Hall current sensor. It has novel structure and beautiful appearance. The whole is composed of shell, iron core, sampling circuit board and fixed resin. The shell material is made of PC/ABS alloy, which has the characteristics of high temperature resistance, high mechanical strength and environmental protection. The core is made of oriented cold bonded silicon steel sheet, which has the characteristics of stable performance, high mechanical strength and extremely high magnetic conductivity. Green pluggable terminal is used for circuit board and external wiring, which is convenient and reliable for on-site wiring. The specific structure is shown in Figure 1 and 2. The appearance of the product adopts split design. Figure 1 is a round pass, which is suitable for passing through the DC system when the primary bus is a cable. , Fig. 2 square pass, suitable for the DC system when the primary bus is copper bar. According to the measurement range of primary current and perforation requirements, the corresponding product type can be selected. This series of sensors can measure the current range of 20A ~ 20000A, the main shape of the phi 20, 40, 60, 64*16, 85*27, 104*36, 140*50 and other specifications, as shown in Figure 3, suitable for different applications.
 


              
                   Fig. 1 circular pass pattern                                            Fig. 2 Square pass pattern                         


                   
       Figure 3 AHKC series open type Hall current sensor

 

1.2 Working principle
  Hall current sensor based on hall effect, electromagnetic induction principle, design of a sensor, according to the principle can be divided into the open loop mode (straight) and closed loop mode (magnetic balance type), open hall current sensor is in a traditional open loop (straight) is improved on the basis of hall sensor, is different from traditional single core, single chip design hall, In order to design a split structure, the iron core is separated and installed symmetrically. The hardware adopts parallel complementary differential input of double Hall chips. The principle of open-type Hall sensor is shown in Figure 4:

 

  Fig. 4 Schematic diagram of open Hall sensor


  When the primary side current IP flows through a long wire, will produce a magnetic field around the wire, the size of the magnetic field and is proportional to the current through the wire, the magnetic field gathered in the circular, through two hall element in the circular air gap measurement, two hall element marks instead placed in the same field, the output signal with complementary characteristics of output voltage by differential amplifier output, Not only can suppress the common mode interference, but also the influence of temperature drift, the output voltage VS accurately reflect the original side current IP. The general rated output is calibrated as DC±5V or DC4-20mA.

 

1.3 Product installation
  Take square-hole products as an example, as shown in Figure 5, open the mounting screw of the open-type Hall current sensor, and remove the lower body of the sensor; The upper body of the open type Hall current sensor is loaded into the primary bus of the distribution system, and the lower body of the sensor is closed. The mounting screws and gaskets of the sensor pass through the fixing holes of the upper and lower bodies, and the upper and lower bodies of the sensor are fixed together. If on-site power off installation is possible, two corresponding threaded holes can be opened on the bronze plate according to the sensor spacing requirements, and the sensor is fixed on the threaded hole of the bus bar through the rear mounting fixing hole to complete the installation of the sensor; If the site requires continuous electric installation, the supporting rubber pad can be embedded between the shell and the bronze plate to ensure that the sensor can work reliably under vibration conditions. The whole installation process is relatively quick and simple.

 

 
Fig. 5 Product installation diagram

 

1.4 Advantages of open type Hall sensor
  Compared with the traditional DC current measurement method generally adopted by shunt or transformer, the open-type Hall sensor has the following advantages:
1) High insulation strength of primary side and secondary side, up to AC 12KV isolation;
2) No insertion loss;
3) Good dynamic performance: the response time is less than 20uS and the tracking speed Di /dt is higher than 20A/ uS
4) There is no need to disassemble the original side cable or bus during installation. It is especially suitable for the transformation and construction of equipment that is not allowed to lose power.

 

2. Product application
   Open-end Hall current sensor is mainly used in the transformation of DC distribution system in factories, such as DC power system transformation in power plants, DC system transformation in substations, communication room transformation, railway locomotive transformation and other projects. It can convert the central edge DC current signal of the system into standard DC± 5V or 4-20mA output. It plays the role of monitoring and electrical isolation, and can be used with multi-loop monitoring instruments or other electrical measuring instruments. 

 

3.Conclusion
  Open-end Hall current sensor plays an important role in the application of DC system because of its simple structure, convenient installation, reliable operation and other good applicability, especially in the renovation project.

 

 

波多野结衣无码电影一区 | 亚洲激情综合图色| 佐山爱一区二区| 黄色视频网站日逼国产| 18禁止午夜福利体验区| 好妞干网av| 国产好爽…又高潮了毛片| 久久国产精久久精产国| 人妻的快乐91| 日本一卡二卡新区乱码剧情| 天堂√8在线中文| 亚洲AV成人无码久久精品a| 久久精品夜色噜噜亚洲a∨| 免费观看毛片网站| 自拍偷拍亚洲熟女骚浪淫| 亚洲操逼视频| 毛片毛片22222| 久久久久久精品免费免费高清秒播| 伊人无码精品久久一区二区| 夜色熟女系列丰满熟妇| 日日澡夜夜爽| 欧美做受69| 西西人体大胆瓣开视频| WW国产精品| 人妻videos人妻| 免费一级成人AA片视频| 亚洲熟妇丰满多毛xxxx| 三年片在线观看大全国语| 午夜福利av电影| AV鲁丝一区鲁丝二区鲁丝四区| 亚洲综合色成在线播放| 亚洲av观看网址| 超薄丝袜足一区二区三区| 人人搞人人操人人搞| 欧美一区二区AAA| www永久777| 999777无码| 久久午夜无码鲁丝片直播午夜精品| 玩成熟老熟女视频二区| haodiaori精品| 饥渴人妻欲求不满在线|